Operating Temperature
-40°C to +90°C

Minimum Bending Radius
6 times the outer diameter.

Colors
Single core Red – black – blue – brown (other colors on request)
Twin core Red – black (other colors on request)

Applicable Standards
Basic design BS 7211
Fire resistant BS 6387 (cat.C-W-Z tested in steel conduit)
Acid gas emission EN 50267-2-1 / IEC 60754-1
EN 50267-2-2 / IEC 60754-2
Smoke density EN 61034-2 / IEC 61034-2

Cable Construction

Conductors
Plain annealed copper wire, stranded according to EN 60228 class 2.

Insulation
Cable Mica/Glass fire resistant tape covered by extruded cross-linked compound type EI5.

Twisting
Only for FIRECEL SR112X two conductors are twisted.

Do you have a question?

Drop us a line by compiling the form below. We will be more than happy to reply to any of your questions!

Applications
➜ FIRECEL SR112 cables are specifically designed, manufactured, and tested for fixed or protected installation in emergency power supply, lighting, and control gear applications.
➜ Ideal for use in buildings, transportation systems, power plants, and other critical infrastructures where fire safety is of utmost importance.